wire ampacity and correction factors

wire ampacity and correction factors

Pass the Test - Journeyman Electrician

31/10/2020 9:27PM

Episode Synopsis "wire ampacity and correction factors"

NEC Journeyman Electrical Questions and Answers with Code References Nothing like this available, listen while you work, shower, drive, hike, work out. Learning without all the fluff and sales pitch garbage that so many others put out. Enjoy this content. All content brought to you by Nathan Hawkins free of charge. NEC Table 310.15(B)(16) Conductor ampacity of 2/0 at dry location (900C)= 195 Amperes NEC Table 310.15(B)(2) The correction factor at ambient temperature (450C) = 0.87 Corrected ampacity = 0.87*195 =170 Amperes